Чем мы можем помочь сегодня?

Which of our Can-Open PLC masters (Quantum/Premium/M340/M580) allow usage of only "Node Guarding" instead of "Heartbeat"?

"Node Guarding" is the oldest protocol which monitor the presence of the Can-Open slaves in the Can-Open fieldbus.
This Protocol is supported by all all our Can-Open  masters. (Quantum/Premium/M340/M580).
The network manager polls  each device (slave)  to check its heath.

The "Heartbeat" is the more recent protocol which monitor the presence of the Can-Open slaves in the Can-Open fieldbus.
This Protocol is supported only by our recent Can-Open  masters. (M340/M580).
This protocol is similar to a client server protocol:
Each device provides a life sign periodically.
The benefits is that it required less bus load than node guarding



Schneider Electric Казахстан

Узнайте больше
Изделие:
Узнайте больше
Изделие:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings