Smart UPS Modular Ultra A7A1 Power Module Error

Product Line:

Smart UPS Modular Ultra


Environment:

All models, all serial numbers


Resolution:

If you see an “A7A1” error on a Power Module, please do not replace the Power Module in question.  This error code occurs when there is a PM with firmware 3.3 (or later) and it cannot get an appropriate response from the IM running with UPS firmware 10.8.  To fix this issue, please upgrade the UPS to 13.2 (or later).  Please follow the process below to upgrade the Firmware.

If the issue persists after upgrading the firmware, please get the Power Module replaced.


NMC/Display Firmware - https://www.apc.com/us/en/faqs/FAQ000261841/
UPS Firmware - https://www.apc.com/us/en/faqs/FAQ000261838/
Different ways to Upgrade UPS Firmware - https://www.apc.com/us/en/faqs/FA164737/

Schneider Electric Казахстан

Узнайте больше
Изделие:
Узнайте больше
Изделие:

Нужна помощь?

Нужна помощь?

Инструмент для подбора продукции

Инструмент для подбора продукции

Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.

Получить коммерческое предложение

Получить коммерческое предложение

Заполните заявку онлайн, и с вами свяжется наш эксперт.

Где купить?

Где купить?

Легко находите ближайшего к вам дистрибьютора Schneider Electric.

Центр поддержки

Центр поддержки

Находите ресурсы поддержки для всех ваших потребностей в одном месте.

  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings