Why is my Battery Frame on my Smart UPS Modular Ultra recognized as battery frame #2?
My XRCC (battery frame communication card) is set to position 1, but is being recognized as frame #2 instead of frame #1.
Product Line:
Smart UPS Modular Ultra
Environment:
All models, all serial numbers
Resolution:
In order for the UPS to recognize your XRCC as frame #1, the frame # setting switch has to be a position 0 (as labeled on the switch itself). That position is at 0 degrees / 3 o'clock / horizontal pointing right. If it points to position 1 on the original battery frame label, the UPS sees that as frame #2 instead of frame #1.
NOTE: You can use any number for a single frame, but if you are using all 6 frames, you'll want to start at position 0/frame 1. If two frames have their switches set to the same position, the system detects that and shows a warning - 0x1072 Invalid Configuration – multiple XR frames with the same address.
The label will be modified as shown below so the switch opening is better aligned with the number used by the UPS
| Switch Position | Label # Old label | Label # New label | Frame Number per UPS |
| 0 | n/a | 1 | 1 |
| 1 | 1 | 2 | 2 |
| 2 | 2 | 3 | 3 |
| 3 | 3 | 4 | 4 |
| 4 | 4 | 5 | 5 |
| 5 | 5 | 6 | 6 |
| 6 | 6 | N/A | not recognized |
Опубликовано для: Schneider Electric Казахстан




Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.