What are the mandatory DFB pin assignments in EcoStruxure Control Expert V16.0?
Issue
When creating a Derived Function Block (DFB) type in EcoStruxure Control Expert V16.0, some variable types can be entered in the Data Editor but are not supported for DFB pins.
For example, variables declared with the types ANY, ANY_INT, ANY_ARRAY, or ANY_BIT can be created in the Data Editor, but analyzing the DFB will fail.
Product Line
EcoStruxure Control Expert
Environment
EcoStruxure Control Expert V16.0
Resolution
For DFB pins, the following assignments are mandatory for the specified data types:
| DFB pin | Mandatory assignment for |
|---|---|
| Input | DeviceDDT, DDT-Reference, REF_TO |
| Output | DeviceDDT, DDT-Array, anonymous array (Array of), DDT-Reference, REF_TO |
| Input/Output | IODDT, DeviceDDT |
Assignments not listed above are optional.
Applicable Conditions
The information above applies to DFB types in EcoStruxure Control Expert V16.0.
Do not use ANY, ANY_INT, ANY_ARRAY, or ANY_BIT as DFB pin data types, as these types are not supported and the DFB analysis will fail.