Some Easy-UPS Online UPS require a one time registration code during installation to allow the UPS output to be turned on. The customer or FSR will contact the Schneider Electric Customer Care Centre to register the UPS. Please see the user manual or the below FAQ on how to complete this registration.

Easy-UPS Registration

If for some reason you are unable to complete the registration, follow the below process on how to temporarily bypass the registration process.

Process:
1. After installation, turn on the Easy-UPS. The Easy-UPS display screen will display a three digit code along with the Online, On Battery, Bypass, and Alarm symbols.
Easy UPS Display Code 4

2. Press and hold the Power, Mute / Esc, Enter, Up, and Down buttons simultaneously for 5 seconds.
Easy UPS Display Code 5
Easy UPS Display Code 6

3. Once the buttons have been pressed for 5 seconds, the registration interface disappears and the normal interface appears.
Easy UPS Display Code 6

4. The Easy-UPS can now be used but as this is temporary solution,this process will have to be repeated once the UPS restarts until the UPS has been successfully registered.

Schneider Electric Казахстан

Узнайте больше
Изделие:
Узнайте больше
Изделие:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings