Наши бренды

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
		
Чем мы можем помочь сегодня?
Why the Schneider PLC USB Driver used for M340 and M580 PLC can’t be seen after installation?

1.Context

In certain conditions, it could happen that the installation of the SchneiderPLCUSBDriverSuite finish without error and getting the message that the driver is well installed like on the following screenshot.

installation

installation

installation

However, the PLC USB Driver can’t be seen inside the driver manager :

driver manager

Even inside the program and features of windows :

program windows

2. How to solve

To solve this problem, please follow the step below :

  • Stop ‘NetAccess Service’ in Services manually.

Service

  • Delete C:\windows\System32\UsbConnect.exe , If you can’t delete it, rename it as other name.

System32

  • Re-install the SchneiderPLCUSBDriverSuite.exe.

3. Product

SchneiderPLCUSBDriverSuite

4. Environment

Windows 10 and above

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings