PME 2024- Tamper detected error. A valid software license could not be found.

Product Line
Power Monitoring Expert 2024
_____________________________________________________________
Environment
License Configuration Tool
_____________________________________________________________
Issue :
A valid software license could not be found.
A valid license could not be found

The system logs are flooded with the error: Tamper detected: FlxDotNetClient.SvcSessionException: MID=0, SID=0, EID=6

_____________________________________________________________
Proposed Solution

Solution 1:

Import the attached 3 certificates to the Trusted Root Certification Authority through the Manage Computer Certificates interface.

  1. VeriSign Universal Root Certification Authority.cer
  2. VeriSign Class 3 Public Primary Certification Authority - G5.cer

DigiCert Trusted Root G4.cer

Trusted Root Certification

Then run the below PowerShell script after getting the exported certificate in the system.

Change the path of the exported file in the following script and run it in PowerShell ISE in administrator mode.

$sst = ( Get-ChildItem -Path C:\certs\roots.sst )

$sst| Import-Certificate -CertStoreLocation Cert:\LocalMachine\Root

Solution 2:
If the previous solution fails, rebuild the certificate chain using a functioning PME system.

From this working PME system, export the three specified certificates. You can find the link below to export the trusted root certificate from the functioning machine.
http://woshub.com/updating-trusted-root-certificates-in-windows-10/

Then run the below PowerShell script in the non-working system after getting the exported certificate in the system:

Change the path of the exported file in the following script and run it in PowerShell ISE in administrator mode

$sst = ( Get-ChildItem -Path C:\certs\roots.sst )

$sst| Import-Certificate -CertStoreLocation Cert:\LocalMachine\Root

Schneider Electric Казахстан

Вложения
VeriSign Universal Root Certification Authority.cer [1.18 KB]
VeriSign Class 3 Public Primary Certification Authority - G5.cer [1.21 KB]
DigiCert Trusted Root G4.cer [1.39 KB]
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings