Чем мы можем помочь сегодня?

PME all versions - Log Inserter won't open in Designer if a Log Acquisition Module (LAM) has too many inputs

Product Line:

Power Monitoring Expert all versions
_____________________________________________________________
Environment:

Designer

_____________________________________________________________
Issue :

Log Inserter won't open in Designer if a Log Acquisition Module (LAM) has too many inputs

In Designer, you will see a 'communications error' dialog. In the system log you will see this error:
Image
_____________________________________________________________
Proposed Solution:
There is a certain limitation on the number of inputs can be connected to a Log Acquisition Module. Try to reduce the number of inputs to below 1500 per Log Acquisition Module. Add a second Log Acquisition Module if further inputs are required.

Schneider Electric Казахстан

Узнайте больше
Изделие:
Узнайте больше
Изделие:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings