Чем мы можем помочь сегодня?

Time sync from PME to TransferPact Active Automatic, EM3570 device causing 1 hr difference in timestamp

Environment:

Power Monitoring Expert 2023, 2024, 2024R2

----------------------------------------------------------------------

Product Line:

TransferPact Active Automatic, EM3570

----------------------------------------------------------------------

Description of the issue:

  1. Connect a TransferPact Active Automatic or EM3570 in the Management Console.
  2. Check the time sync with PME.

Image 1

Image 2

----------------------------------------------------------------------

Workaround:

  1. Open the .XML file for that device type, either from the config\translator folder if using a modified file or from the system\translator folder.
  2. Change the DeviceTimeLocale to "Local" in the XML file as shown in the attached screenshot below.
  3. Restart the ION Network Router service.

Image 3

Image 4

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings