Чем мы можем помочь сегодня?

Frequency Reading Not Displayed During Testing

Article available in these languages:

  • Испанский

Issue:

The P3 relay does not show frequency readings during a real or virtual injection test.

Product:

PowerLogic™ P3 Relay

Environment:

Testing scenario using virtual or secondary voltage injection.

Cause:

The frequency is not measured if:

  • The maximum of the three phase-to-phase or phase-to-neutral voltages is less than 5.5 × (VT primary / VT secondary) (primary voltage reference).
  • The secondary voltage injection is less than 5.5 V.

This is a design condition to ensure accurate frequency measurement.

Resolution:

Increase the magnitude of the injected voltage during the virtual injection test. After raising the voltage above the required threshold, the frequency readings will appear as expected.

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings