Чем мы можем помочь сегодня?

How do I access a bit from a word in Operator Terminal Expert?

Issue:

How do I access a bit from a word in Operator Terminal Expert?

Product:

Operator Terminal Expert

Resolution:

We can define a bool variable pointing to a specific bit of a word, but this requires creating a new variable. You can see below Var1 is accessing a bit from Var2

Non IEC Syntax

Bit from word

IEC Syntax:

Bit from word IEC

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Казахстан

Узнайте больше
Изделие:
Узнайте больше
Изделие:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings