Troubleshooting SAGE 4400 RTU Using LED Indicators
Issue:
How to interpret LED indicators on the SAGE 4400 RTU for troubleshooting purposes.
Product:
SAGE 4400 RTU
Environment:
Substation automation systems using SAGE 4400 RTU for monitoring and control.
Cause:
Users may encounter operational issues and need a quick method to diagnose problems without advanced tools.
Resolution:
The SAGE 4400 front panel includes LEDs that provide real-time status for communication ports and system conditions:
- Comm LEDs (per RS232 port):
- DCD/+5V: Data Carrier Detect or +5V output
- RX: Receive activity
- TX: Transmit activity
- RTS: Request to Send
- CTS: Clear to Send
- System LEDs:
- Power: Indicates RTU power (normally ON)
- Run: CPU running (blinking = normal; steady ON = Safe/Recovery mode; OFF = CPU not running)
- Reset: Illuminates during reset signal (normally OFF)
- Local: Indicates Local/Remote switch position (Local disables controls)
- Time Source Failed: Configured time source failure
- IED Failed: Communication failure with one or more IEDs
- Alarm 1 & 2: Relay energized status
- User Logged In: Active user session
- Config Changed: New configuration XML file loaded but not yet activated
- RLL Running: ISaGRAF logic program active
- Ethernet Link: Valid Ethernet connection detected
Use these indicators to quickly identify power, communication, configuration, or control issues before performing deeper diagnostics.
Опубликовано для: Schneider Electric Казахстан
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.