Чем мы можем помочь сегодня?

PME 2024 - Installer steps "Update File Permissions" and "Registering Windows Services" are unsuccessful

Issue

During a fresh install, the "Update File Permissions" and "Registering Windows services" steps are unsuccessful. None of the PME Windows services are installed. The install log shows errors:

  • Update File Permissions fail: MethodHandler encountered a problem while calling 'Installer.InstallTools.WinUtilities.AssignReadWriteFolderControl': InstallTools.Utility.VariableInterpolationException: Variable lookup does not contain a definition for the variable 'globalNetworkServiceLocalizedNameNoDomain' --- > System.Collections.Generic.KeyNotFoundException: The key 'globalNetworkServiceLocalizedNameNoDomain' was not found in VariableLookup.
    • <AssignReadWriteFolderControl>
      Library="WinUtilities"
      Class="Installer.InstallTools.WinUtilities"
      UIMessageOnFail="Could not set user permissions on Config folder">
      <userName>@globalNetworkServiceLocalizedNameNoDomain/@</userName>
      <folderName>@globalProgramFileFolder/@\Applications\Dashboards\App_Data</folderName>
      </AssignReadWriteFolderControl>
  • Variable lookup does not contain a definition for the variable 'globalLocalSystemLocalizedName' ---&gt; System.Collections.Generic.KeyNotFoundException: The key 'globalLocalSystemLocalizedName' was not found in VariableLookup

Registering Windows Services error

Product Line

Power Monitoring Expert 2024

Environment

Install/Upgrade

Cause

The Windows account used to run the installer is the built-in Administrator account. For cybersecurity reasons, this account has restrictions on it and shouldn't be used to perform software installations. It's primarily intended for initial system provisioning or disaster recovery.

Resolution

Run the installer with a local Windows user:

  1. Open the Windows Start Menu, search for and open "Computer Management"
  2. Open Local Users and Groups > Users
  3. Right-click > New User
  4. Enter a User name and a password that meets the minimum requirements per the IT policy, then uncheck "User must change password at next logon".
  5. Click Create then close the window.
  6. Add this user to the local Administrators group.
  7. Add this user to SQL Server with sysadmin permission.
  8. Shift + right-click the MainSetup.exe of the PME installer > Run as different user > enter the credentials for the newly created user

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:

Нужна помощь?

Нужна помощь?

Инструмент для подбора продукции

Инструмент для подбора продукции

Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.

Получить коммерческое предложение

Получить коммерческое предложение

Заполните заявку онлайн, и с вами свяжется наш эксперт.

Где купить?

Где купить?

Легко находите ближайшего к вам дистрибьютора Schneider Electric.

Центр поддержки

Центр поддержки

Находите ресурсы поддержки для всех ваших потребностей в одном месте.

  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings