How to Identify the Correct Device Type for Micrologic Trip Unit

Issue:

Sometimes when connecting a Micrologic Trip Unit to a system such as, Power Monitoring Expert (PME), it can present an error message "Translator Failure" or not show the proper values. This may be an indication that the incorrect device type is being used for this device in the program. To verify if this is the case, the device type for the unit can be identified by reading a specific Modbus register.


Product Line:
Micrologic A

Micrologic E

Micrologic P

Micrologic H

Environment:
Modbus Reading Program

Resolution:

To do this process, you will need a tool that can read Modbus registers. If you do not have a preferred program for this action, you can download the attached Modbus Tester program from this article Video: What is Modbus Tester and how do I use it? | Schneider Electric USA.

In order to figure out which trip unit product is being used, we will need to identify which Modbus register will return the proper code. On pg. 136 of the user guide found in the link and attached to the article, What are the Modbus registers for Micrologic A, P, and H trip units used in Powerpact P, R, and Masterpact NW/NT breakers? | Schneider Electric USA, under the "Product Identification" section it shows the register to read to get the device type returned to you for identification.

In the screenshot below, when you read Holding Register (R03 / W16): 8716 (full register value being 408716) it will return the type of the trip unit. Based on the number returned you will be able to identify if it is one of the trip unit types below Micrologic A, Micrologic E, Micrologic P, or Micrologic H.

product identification

Schneider Electric Казахстан

Вложения
All A, P, H Registers (1).pdf [9.51 MB]
Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings