How to fix Maximum Connection Reached Error on NMC When Trying To Enter the Web Interface
Issue:
How to fix Maximum Connection Reached Error on NMC When Trying To Enter the Web Interface
Product Line:
Network Management Card 2 (NMC2) - AP9630/AP9631 version 6.x.x above
Network Management Card 3 (NMC3) - AP9640/AP9641 version 1.x.x.x above
Environment:
All serial numbers
Cause:
Resolution:
You can clear active or stuck user sessions directly from the NMC CLI. The following steps highlight how to delete active or stuck user session in Web Interface to accept new connections.
1. Open an SSH or Telnet client (e.g., PuTTY) and connect to the NMC IP address.
2. Log in using the NMC username and password.
3. Type "session" to view active connections.
4. Type "session -d [ID]" to delete a specific session (e.g., session -d 9).
Note: Repeat steps until all unnecessary web sessions have been removed.
5. Once no active sessions, exit the CLI or SSH.
6. Re-log in to the NMC Web Interface and confirm that access is restored.
Kindly make sure that "Allow Concurrent Logins" is enabled. You can enable it using web access under Configuration → Security → Session Management. Enable "Allow Concurrent Logins" and click Apply. Verify the setting is saved successfully.
Note: Allow Concurrent Logins enables multiple users or sessions to be logged in to the NMC simultaneously. When this setting is disabled, only one active login session is permitted at a time, and any additional login attempts may be denied until the existing session is terminated.
Normally, this issue can be resolved by reseating the card or rebooting it through SSH, Telnet or the pinhole button.
Should there be any other questions and/or concerns, feel free to reach out to us at 1-800-800-4272 or our chat with our technical support group atAPC by Schneider Electric Customer Technical Support
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.