How do I configure and use Harmony XB5R/XB4R wireless pushbuttons?
1. What you need to know
Harmony XB4R (metal) and XB5R (plastic) pushbuttons are wireless and battery less: pressing the button generates the energy needed to send a radio frame to the receiver, which converts it into an output for a PLC input or a control circuit. No wiring and no battery maintenance are required. Configuration consists of pairing each transmitter with a receiver channel, then selecting the output mode.
2. How it works and how it is set up
The range is built on energy harvesting: the mechanical action of the operator generates the energy for one radio transmission. Only the receiver is wired and powered.
- Each transmitter sends a unique identifier, so a receiver only reacts to the transmitters paired with it.
- Transmitters can be mounted on moving or remote parts of a machine where cabling is impractical.
- Pairing and output settings are stored in the receiver and survive a power loss; output states do not.
See each configuration step below:
- How to pair and unpair a Harmony ZBRT1 or ZBRT2 transmitter?
- How to configure a Harmony ZBRRA receiver?
- How to duplicate an electrical function using Harmony XB5R?
- How to lock and unlock a Harmony ZBRRA or ZBRRC receiver?
- How to replace a Harmony ZBRT1 or ZBRT2 transmitter?
- How to reset a Harmony ZBRRA and ZBRRC receiver?
- How to adjust your equipement using ZBRT2 transmitters?
- How to Install ZBRV1 on ZBRT to receive visual feedback
NB : ZBRRD has been discontinued since June 2026.
3. Choosing the receiver
| Criterion | ZBRRA | ZBRRC |
|---|---|---|
| Output type | 2 changeover relays, 3 A | 4 PNP solid-state, 200 mA |
| Supply voltage | 24…240 V AC/DC | 24 V DC |
| Output modes | Monostable, Bistable, Enable/Disable | Monostable |
4. Schneider Electric references
| Function | Reference | Description |
|---|---|---|
| Receiver, relay outputs | ZBRRA | 2 changeover relay outputs 3 A, 24…240 V AC/DC |
| Receiver, solid-state outputs | ZBRRC | 4 PNP outputs 200 mA, 24 V DC |
| Transmitter | ZBRT1 | Wireless and battery less transmitter, without head, simple action |
| Transmitter | ZBRT2 | Wireless and battery less transmitter, without head, double action |
| Transmitter | ZBRV1 | Visual feedback for ZBRT transmitters |
| Antenna | ZBRA1 | Relay antenna to extend radio range |
Launch Product Selector on se.com to configure a Harmony XB4R or XB5R solution or contact Schneider Electric Technical Support.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.