How to configure the History Trend to display archived values

Question

Why are archived values not displayed in the History Trend?

Answer

If archived values are not displayed in the History Trend, verify that the HMI History Trend configuration has been created and that the correct Configuration Name is used in the CAT LogData.

Follow these steps:

  1. In your project, go to Program_Archive > Configuration > HMI History Trend, right-click on HMI History Trend, and select Open.

Open_HMI,History trend

  1. In the HMI History Trend window, click Add Item and configure the popup according to the screenshot below.

History Trend config

  1. Copy the Configuration Name. In my example, the configuration name is "HistoryTrendConfigTest".

History trend name

Paste the same configuration name into the Configuration Name property of the History Trend in your CAT LogData.

History trend fp

Once this configuration is done, the issue should be resolved.

trend