How can we help you today?

Factory default settings for Micrologic trip units 5.2, 5.3, 6.2, 6.3 electronic trip units on Powerpact H, J, and L frame breakers.

Issue:
Factory default settings for Micrologic trip units 5.2, 5.3, 6.2, 6.3 electronic trip units on Powerpact H, J, and L frame breakers.

Product Line:
Circuit Breakers

Environment:
Powerpact H, J and L with Micrologic trip units

Cause:
Discovery of factory default settings

Resolution:

Factory Default settings for 5.x and 6.x:
Ir = 1.0 x In
tr = 0.5 seconds

Isd = 6 x Ir
tsd =  Off, 0 seconds

Ii = 1.5 x In

For 6.2:
Ig = .3 x In
tg = Off, 0 seconds

For 6.3
Ig = .2 x In
tg = Off, 0 seconds

Schneider Electric Macedonia

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.