How can we help you today?

There is somthing confusing about the current derating with the altitude > 1000m. The data in catalogue is 2.2% per additional 100m while in manual ...

Goals and Symptoms

There is somthing confusing about the current derating with the altitude > 1000m. The data in catalogue is 2.2% per additional 100m while in manual is 0.5%.
Which one is right?

Facts and Changes

ATS48
Altitude

Causes and Fixes

These both values are bad. The real derating is 2% per additional 100 meter.