What is the purpose of the external battery of the M221?

The help content gives us the information that the battery of the M221 allows:
- to save the content of the whole %MW area ( %MWi with i>50;  note: %MW0-%MW49 are also save without battery)
- to save the RTC clock

In reality the battery is always needed/mandatory because without battery the PLC can’t start in RUN after a Power Cycle.
Within %S75 the PLC program can check when the battery has the be replaced before it becomes out of order (average is every 4/5 years):
=> when this bit is Set to 1, it means the external battery power is low and it has to be replaced soon.

Note:

This info is valid for the versions prior to SoMachine Basic - V1.3 SP1 - build 44532 and Functional level lower than V3.1.

From SoMachine Basic - V1.3 SP1 and with the Functional level V3.1, a new Starting mode is available:

Unconditional Start In Run : The logic controller automatically starts application execution even if the controller battery is absent or discharged.

Unconditional Start in Run