Can the SoMachine V4.3 / EcoStruxure Machine Expert array size be changed at runtime?

This can be achieved by assigning a Symbol (tag/variable) inside the definition of the array.
Example - this is the declaration of a dynamically sized Array of INTs:

VAR
iArrayIndex1 : INT;
MyIntArray : ARRAY [0..iArrayIndex1] OF INT;
END_VAR

NOTE:
1) Dynamic Arrays will not work with variable sharing to HMI via the Symbol Configuration Node. Vijeo Designer and EcoStruxure Operator Terminal Expert do not handle Dynamic Arrays.
2) If you are using Dynamic Arrays inside Functions or Function Blocks, the instantiated memory size for a called Function or Function Block is limited, so limit the maximum value of the index accordingly and test your application thoroughly.

Schneider Electric Macedonia

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Get a Quote

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings