ATV630- How do you set up the run command on DI1?
Issue:
ATV630 set up the run command on DI1.
Product Line:
ATV630
Environment:
2-wire control
Cause:
n/a
Resolution:
Suggest to go to menu 5.5 and set 2-wire control to 2-wire and set 2-wire type to Level. This will automatically assign DI1 to run forward.
ATV630 set up the run command on DI1.
Product Line:
ATV630
Environment:
2-wire control
Cause:
n/a
Resolution:
Suggest to go to menu 5.5 and set 2-wire control to 2-wire and set 2-wire type to Level. This will automatically assign DI1 to run forward.