What is the behavior of the FPI if the parameter cross-country fault detection is disabled?
  • This option is used to enable detection of "double" fault currents, i.e. 2 simultaneous phase-to-ground faults on 2 phases and at 2 different locations on the network.
  • In case of double fault on 2 different locations of the network, the 2 directions will be indicated.
  • In all cases this generates 2 phase faults. With this option the cross-country fault alarm will be set in addition to the phase faults.
Note: cross-country fault detections are only available on instance 3 of a zero sequence fault (in ammetric fault detection).
This case should not be confused with what is called "double fault" in France, which is referring to 2 faults in sequence

Schneider Electric Macedonia

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

  • Get a Quote

    Start your sales enquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings