What is the behavior of the FPI if the parameter cross-country fault detection is disabled?

  • This option is used to enable detection of "double" fault currents, i.e. 2 simultaneous phase-to-ground faults on 2 phases and at 2 different locations on the network.
  • In case of double fault on 2 different locations of the network, the 2 directions will be indicated.
  • In all cases this generates 2 phase faults. With this option the cross-country fault alarm will be set in addition to the phase faults.
Note: cross-country fault detections are only available on instance 3 of a zero sequence fault (in ammetric fault detection).
This case should not be confused with what is called "double fault" in France, which is referring to 2 faults in sequence

Schneider Electric Macedonia

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Get a Quote

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings