EcoStruxure Hybrid DCS [2018] How to fix the error that 'A time stamped variable must be mapped on the address %SW73.7'
- Issue
- Product Line
- Environment
- Refine the built program, create a test variable Bool type and assign address %SW73.7.
- Right click and go to customize columns, select time stamping and enable for this variable, and make it both edges.
After all, building the executable to check whether the error has been fixed.