How to connect my Control Expert client to the server ?

Before launching Control Expert Topology Manager (TM) on the client side , please perform the following sequence :

1- Close TM on the server side

2- Open Server Configuration

3- Modify the Listening IP address in the Listening Connections tab : Either select the ethernet card with which you are communication with the client PC or type 0.0.0.0 to listen to all ethernet cards.

Server Configuration listenning IP address

4- Apply and close the tool.

5- Open TM on the client side and open User Preferences ;

6- Modify the Networkds And Servers tab, and modify the Control expert Server Address with the IP :

Here the IP address of my server is 192.168.189.1, the port to use is 19950.

User Preferences define IP address of TM server

7- Close and relaunch TM on the client side, and now you should be able to connect to the server.

Schneider Electric Macedonia

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

  • Get a Quote

    Start your sales enquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings