Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Smart UPS Modular Ultra A7A1 Power Module Error
Product Line:

Smart UPS Modular Ultra


Environment:

All models, all serial numbers


Resolution:

If you see an “A7A1” error on a Power Module, please do not replace the Power Module in question.  This error code occurs when there is a PM with firmware 3.3 (or later) and it cannot get an appropriate response from the IM running with UPS firmware 10.8.  To fix this issue, please upgrade the UPS to 13.2 (or later).  Please follow the process below to upgrade the Firmware.

If the issue persists after upgrading the firmware, please get the Power Module replaced.


NMC/Display Firmware - https://www.apc.com/us/en/faqs/FAQ000261841/
UPS Firmware - https://www.apc.com/us/en/faqs/FAQ000261838/
Different ways to Upgrade UPS Firmware - https://www.apc.com/us/en/faqs/FA164737/

Schneider Electric Macedonia

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:

Need help?

  • Get a Quote

    Start your sales enquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings