How to resolve “Bits number (%I,%M) must be aligned on paragraph of 128 bits” after upgrading the M580 firmware in a project?
Issue:
After upgrading the M580 firmware version configured in EcoStruxure Control Expert, the following error may be reported during a project build:
Parameter <Number of outputs bits> in error (RIO bus S908 Support in M580: the Bits number (%I,%M) must be aligned on paragraph of 128 bits (and >=128))
This error may appear when upgrading a project from an M580 firmware version prior to v2.30 to a higher version.
This issue applies only to M580 PLCs that support S908 drops.
Product:
M580 controller
Environment:
EcoStruxure Control Expert software (previously Unity Pro)
Resolution:
Verify the configured size of the %I and %M State RAM areas.
Starting with M580 firmware v2.20, the number of bits must be 128 or greater and aligned to a multiple of 128 due to changes implemented to the S908 memory usage.
Adjust the affected memory size to an appropriate multiple of 128.
Example:
If %M is configured to 1008, it is not correctly aligned. Change the value to 1024, which is a multiple of 128.
After changing the memory configuration, the project can be rebuilt without errors.
Note: Transferring the rebuilt project will require the PLC to stop.