Roll over image to zoom in

M9P22606
Environmental Data
Total lifecycle Carbon footprint
16
Use Better
Packaging made with recycled cardboard
Yes
Use Again
Recyclability potential, in %
53
Take-back
No
This Multi9 N40N is a low voltage miniature circuit breaker (MCB). It is a 1P+N circuit breaker with 1 protected pole, 6A rated current and C tripping curve. The rated short circuit breaking capacity is up to 10kA at 240VAC conforming to EN/IEC 60947-2 standard. This product complies with industrial standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting equipment from electrical threats. This product protects from short circuit and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 20000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 4kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 2 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 18mm x (H) 81mm x (D) 78mm. The weight is 0.115kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -25°C to 70°C. The storage temperature is -40°C to 70°C.
Range | Multi9 |
---|---|
Product name | Multi9 N40 |
Product or component type | Miniature circuit-breaker |
Device short name | N40N |
Device application | Distribution |
Poles description | 1P + N |
Number of protected poles | 1 |
Neutral position | Left |
[In] rated current | 6 A at 50 °C conforming to EN/IEC 60947-2 |
Network type | AC |
Network frequency | 50/60 Hz |
Trip unit technology | Thermal-magnetic |
Curve code | C |
Breaking capacity | 10 kA Icu at 240 V AC 50/60 Hz between phase and neutral conforming to EN/IEC 60947-2 |
Standards | EN/IEC 60947-2 |
[Ue] rated operational voltage | 240 V AC 50/60 Hz between phase and neutral |
---|---|
Magnetic tripping limit | 8.5 x In +/- 20 % AC |
[Ics] rated service breaking capacity | 7.5 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz |
Limitation class | 3 conforming to EN/IEC 60947-2 |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 4 kV conforming to EN/IEC 60947-2 |
Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
Contact position indicator | Yes |
Control type | Toggle |
Local signalling | ON/OFF indication |
Mounting mode | Clip-on |
Mounting support | DIN rail |
9 mm pitches | 2 |
Height | 81 mm |
Width | 18 mm |
Depth | 78 mm |
Net weight | 0.115 kg |
Colour | Grey |
Mechanical durability | 20000 cycles |
Electrical durability | 20000 cycles |
Provision for padlocking | Padlockable |
Connections - terminals | Tunnel type terminal (top or bottom)0.75…16 mm² - rigid Tunnel type terminal (top or bottom)0.33…10 mm² - flexible Tunnel type terminal (top or bottom)0.33…10 mm² - flexible with ferrule |
Wire stripping length | 13 mm for top or bottom connection |
Tightening torque | 2 N.m top or bottom |
Earth-leakage protection | Separate block |
IP degree of protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529 |
---|---|
Pollution degree | 3 conforming to EN/IEC 60947-2 |
Tropicalisation | 2 conforming to IEC 60068-1 |
Relative humidity | 95 % at 55 °C |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -40…70 °C |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 1.800 cm |
Package 1 Width | 7.400 cm |
Package 1 Length | 9.000 cm |
Package 1 Weight | 113.000 g |
Unit Type of Package 2 | BB1 |
Number of Units in Package 2 | 12 |
Package 2 Height | 7.800 cm |
Package 2 Width | 9.200 cm |
Package 2 Length | 22.500 cm |
Package 2 Weight | 1.401 kg |
Unit Type of Package 3 | S03 |
Number of Units in Package 3 | 144 |
Package 3 Height | 30.000 cm |
Package 3 Width | 30.000 cm |
Package 3 Length | 40.000 cm |
Package 3 Weight | 17.308 kg |
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Total lifecycle Carbon footprint
16
Use Better
Packaging made with recycled cardboard
Yes
Packaging without single use plastic
No
Compliant with Exemptions
SCIP Number
C839c050-8547-41ce-b0db-e9813554fc09
REACh Regulation
Use Again
Recyclability potential, in %
53
End of life manual availability
No need of specific recycling operations
Take-back
No
WEEE Label

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Items usually bought together
Need more information? Check our technical FAQs!
Easily find answers to the most frequently asked questions.