Roll over image to zoom in

METSEPM5350
Feature-rich power and energy meters
Identify energy savings opportunties with precision accuracy of Class 0.5S
Total Harmonic Distortion for Power Quality management
Full scape graphical LCD for clear viewing
Environmental Data
Use Better
Packaging made with recycled cardboard
No
Use Again
Take-back
No
This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 32 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency and Power Factor. Include a non-volatile memory for several parameters and alarms. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 85 to 265 VAC and 100 to 300 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 20V AC to 480V AC, CAT III or 20V AC to 690V AC, CAT II at 45 Hz to 70 Hz. The range of measurement voltage between Phase and Neutral is 20V AC to 277V AC, CAT III or 20V AC to 400V AC, CAT II at 45 Hz to 70 Hz. Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support. The meter also has four digital inputs and dual relay outputs. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 2.24 inches (57 millimetres), height 3.78 inches (96 millimetres) and product weight 8.8 onces (250 g).
Range | PowerLogic |
---|---|
Product name | PowerLogic PM5350 |
Device short name | PM5350 |
Product or component type | Power meter |
Power quality analysis | total demand distortion total harmonic distortion |
---|---|
Device application | Power monitoring |
Type of measurement | Current Voltage Frequency Power factor Energy Apparent power Active power Reactive power |
supply voltage | 85...265 V AC 45...65 Hz 100...300 V DC |
Network frequency | 50 Hz 60 Hz |
[In] rated current | 5 A 1 A |
type of network | 1P + N 3P + N 3P |
Maximum power consumption in VA | 11.9 VA |
Ride-through time | 100 ms 120 V AC typical 400 ms 230 V AC typical 50 ms 125 V DC typical |
Display type | Monochrome graphic LCD |
Display resolution | 6 lines |
Sampling rate | 32 samples/cycle |
Measurement current | 5…9000 mA |
Analogue input type | Current 0.05...9 A (impedance <= 0.3 mOhm) Voltage (impedance 10 MOhm) |
Measurement voltage | 35…480 V AC 45...65 Hz phase to phase 20…277 V AC phase to neutral |
Frequency measurement range | 45…70 Hz |
Number of inputs | 4 digital |
Measurement accuracy | Current +/- 0.3 % Voltage +/- 0.3 % Frequency +/- 0.05 % Power factor +/- 0.005 Active energy +/- 0.5 % Reactive energy +/- 2 % Active power +/- 0.5 % Apparent power +/- 0.5 % Apparent energy +/- 0.5 % Reactive power +/- 2 % |
Accuracy class | Class 0.5S active energy conforming to IEC 62053-22 Class 0.5 active energy conforming to IEC 61557-12 Class 2 reactive energy conforming to IEC 62053-23 Class 2 reactive energy conforming to IEC 61557-12 Class 0.5 power conforming to IEC 61557-12 |
Number of outputs | 2 relay |
Communication port protocol | JBUS Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds |
Communication port support | Terminal block: RS485 |
Data recording | Min/max of instantaneous values Alarms |
Connections - terminals | Voltage circuit: screw terminal block4 Control circuit: screw terminal block2 Current transformer: screw terminal block6 Input/output circuit: screw terminal block6 Relay output: screw terminal block4 |
Mounting mode | Flush-mounted |
Type of installation | For indoor use in a stationary panel |
Standards | IEC 61010-1 |
Product certifications | CE CULus |
Width | 96 mm |
Depth | 44 mm |
Height | 96 mm |
Net weight | 0.25 kg |
Electromagnetic compatibility | Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3 Electrostatic discharge conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5 Conducted RF disturbances conforming to IEC 61000-4-6 Immunity to impulse waves conforming to IEC 61000-4-12 Conducted and radiated emissions class A conforming to EN 55011 Limits for harmonic current emissions conforming to IEC 61000-3-2 |
---|---|
Overvoltage category | III |
IP degree of protection | IP30 rear: conforming to IEC 60529 IP54 display: conforming to IEC 60529 |
Relative humidity | 5…95 % at 50 °C non-condensing |
Pollution degree | 2 |
Ambient air temperature for operation | -25…70 °C meter -20…70 °C display -25…-20 °C (with reduced performance) display |
Ambient air temperature for storage | -40…85 °C |
Operating altitude | <= 3000 m |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 11.200 cm |
Package 1 Width | 12.500 cm |
Package 1 Length | 12.700 cm |
Package 1 Weight | 346.000 g |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 12 |
Package 2 Height | 30.000 cm |
Package 2 Width | 30.000 cm |
Package 2 Length | 40.000 cm |
Package 2 Weight | 4.829 kg |
Warranty | 18 months |
---|
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Environmental Disclosure
Use Better
Packaging made with recycled cardboard
No
Packaging without single use plastic
No
Compliant with Exemptions
SCIP Number
A625a530-88d0-44af-8a48-7177db082926
REACh Regulation
PVC free
Yes
Use Again
Take-back
No
WEEE Label

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Need more information? Check our technical FAQs!
Easily find answers to the most frequently asked questions.