Power quality meter, PowerLogic PM8000, Advanced, integrated display, 512 MB, 512 s/c

METSEPM8340

Fast access to timely, critical information for energy, electrical network, and asset management
Help operations personnel avoid downtime by making power quality understandable
Makes energy and power quality actionable to support your op and sustainability goals
More detailed PQ compliance reporting, and expertlevel power quality and rootcause analytics
Forecasting to help ensure your electrical system avoid overloads, unbalances or high peak demand
Environmental Data
Total lifecycle Carbon footprint
298
Use Better
Packaging made with recycled cardboard
information_stroke
Recycled cardboard content is minimum 70% (50% in US). Some orders may include non-recycled cardboard until stock runs out.
No
Use Again
Take-back
information_stroke
Whether the product has been included in a global take-back program. Some products are eligible in some geographies, please verify if it's available in your country.
No
Description
arrow2_down
The PowerLogic PM8340 comes in a flush mount form factor with integrated display. It is designed to help you ensure reliability and efficiency of your power-critical facilitiy. It unlocks energy transparency and provides actionable data from complex power quality conditions. With its modular, flexible, and power ION technology, you can build custom applications for each meter. It comes with revenue grade accuracy, multiple communication ports, and a color graphical display. This meter also feature onboard power quality analysis as well as a patented Disturbance Direction Detection. Certified by third party labs for Class 0.2S energy accuracy (IEC62052-11, IEC62053-24, IEC62053-22). Certified also for power quality (IEC62586-2, IEC61000-4-30 Class A). Cybersecurity features include secure protocols (HTTPs, sFTP, Secure ION), security event logging, Syslog protocol. Ability to enable/disable communication ports and support 50 configurable user account to help manage access. With 512MB of memory to support up to 64 data logs (1024 channels), 50+ user-definable alarms, waveform captures upto 512 samples/cycle, 1/2 cycle RMS logging. The storage can also be used for custom web pages, min/max logs, energy trends, and Time of Use. The ability to timestamp events to +/-1ms utilizing time synchronization. Time synch method that include PTP (IEEE1588), NTP, IRIG-B, GPS ASCII (RS485) and network time set function. 3 digital inputs and one digital output, plus the ability to add up to 4 option modules. I/O option modules include 2 relays and 6 digital inputs or 2 analog outputs and 4 analog inputs Wide control power range of 90-415 VAC / 110-415 VDC. Operating environment of -25 to +70°C; Humidity rating of 5% to 95%; Altitude up to 3000 m.
Specifications
arrow2_down
Main
RangePowerLogic
Product namePowerLogic PM8000
Product or component typePower meter
Device short namePM8340
Market segmentBuildings large building cost management: billing: sub feeder
Buildings small building network management: main incomer
Buildings medium building network management: main incomer
Buildings large building network management: main incomer
Buildings large building network management: sub feeder
Buildings multi-site network management: main incomer
Buildings multi-site network management: sub feeder
Data center network management: main incomer
Data center small building network management: sub feeder
Healthcare large building network management: main incomer
Healthcare multi-site network management: sub feeder
Industry multi-site network management: main incomer
Industry network management: sub feeder
Utility network management: sub feeder
model typeAdvanced
Complementary
Power quality analysisconforming to EN 50160: 2010 compliance report
conforming to IEEE 519: 2014 compliance report
conforming to IEC 61000-4-30: class A power quality measurement
up to the 63rd harmonic
conforming to IEC 61000-4-15 harmonic distortion
conforming to EN 50160: 2010 waveform capture
conforming to IEEE 519: 2014 voltage sag and swell detection
programmablity (logic and math functions)
conforming to IEC 62586 power quality monitoring
disturbance direction detection
conforming to IEC 61000-4-15 flicker
rapid voltage change
Device applicationPower monitoring
WAGES metering
Type of measurementCurrent per phase, rms
Voltage
Frequency total
Active and reactive power total
Apparent power total
Power factor total
Active and reactive power per phase, rms
Apparent power per phase, rms
Power factor per phase, rms
supply voltage90...415 V AC 45...65 Hz +/- 10 %
110...415 V DC +/- 10 %
Network frequency50 Hz
60 Hz
[In] rated current1 A
5 A
10 A
Poles description3P + N
3P
1P + N
Power consumption in VA16 VA at 230 V AC
Display typeColour TFT LCD
Display resolution320 x 240 pixels QVGA
Sampling rate512 samples/cycle
Measurement current50…10000 mA
Analogue input typeVoltage (impedance 5 MOhm)
Current (impedance 0.3 mOhm)
Measurement voltage57…400 V AC 42...69 Hz between phase and neutral
100…690 V AC 42...69 Hz between phases
Frequency measurement range42…69 Hz
Number of inputs3 digital 30 V AC
3 digital 60 V DC
Measurement accuracyCurrent +/- 0.1 %
Voltage +/- 0.1 %
Active energy +/- 0.2 %
Accuracy classClass 0.2S active energy conforming to IEC 62053-22
Class 0.2 active energy conforming to ANSI C12.20
Class 0.2 active power conforming to IEC 61557-12
Class 0.5S reactive energy conforming to IEC 62053-24
Class 0.5 power factor conforming to IEC 61557-12
Class 0.2 voltage conforming to IEC 61557-12
Class 0.2 current conforming to IEC 61557-12
Number of outputs1 pulse
Information displayedVoltage
Current
Frequency
Power
Energy consumption
Harmonic distortion
Communication port protocolModbus RTU at 115 kbauds - 2-wire
ION at 115 kbauds - 2-wire
DNP3
IEC 61850
Modbus TCP/IP
Ethernet Modbus TCP/IP daisy chain at 10/100 Mbit/s
RSTP 801.1d 2004
Communication port supportETHERNET
Screw terminal block: RS485
Communication network typeIPv6 (internet protocol)
Data recordingMin/max of instantaneous values
Waveform logs
Sequence of event recording
Time stamping
Alarm logs
Trending/forecasting
Sag and swell logs
Harmonics logs
GPS synchronisation
Data logs
Event logs
64 data recorders
Memory capacity512 MB
Web servicesCustomizable home page
File upload/download via FTP
File upload/download via SFTP
Web server
Alarm notification by e-mail
Viewing of captured waveform (FTP)
Viewing of captured waveform (web)
HTTPS server
Communication serviceSMTP e-mail notification
RSTP support
NTP time synchronization
DHCP
PTP time synchronization
CybersecurityEnable/disable communication ports
Password protection
Syslog protocol support
Robust security logs
Port hardening
Mounting modeFlush-mounted
Mounting supportFramework
Installation categoryIII
Safety ConstructionIII400…690 V conforming to IEC 61010-1:ed. 3
III400…690 V conforming to EN 61010-1:ed. 3
III347…600 V conforming to UL 61010-1:ed. 3
III347…600 V conforming to CSA C22.2 No 61010-1:ed. 3
StandardsIEC 61557-12
IEC 62052-11
IEC 62053-24
IEC 62053-22
IEEE 1588
IEC 62586-2
IEC 61326-1
Product certificationsCE
CULus
N998
Width96 mm
Depth77.5 mm
Height96 mm
Net weight581 g
Environment
Electromagnetic compatibilityElectrostatic discharge conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
Surge immunity test conforming to IEC 61000-4-5
Conducted RF disturbances conforming to IEC 61000-4-6
Magnetic field at power frequency conforming to IEC 61000-4-8
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Immunity to impulse waves conforming to IEC 61000-4-12
Conducted and radiated emissions (2...150 Hz) conforming to EN 55022
Conducted and radiated emissions conforming to EN 55011
Conducted and radiated emissions conforming to FCC part 15
Conducted and radiated emissions conforming to ICES-003
Conducted RF disturbances (2...150 Hz) conforming to CLC/TR 50579
Surge withstand conforming to IEEE C37.90.1
IP degree of protectionIP54 front: conforming to IEC 60529
IP30 body: conforming to IEC 60529
Relative humidity5…95 %
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Operating altitude3000 m
Compatibility codePM8240
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height13.900 cm
Package 1 Width14.300 cm
Package 1 Length18.900 cm
Package 1 Weight858.000 g
arrow2_down
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Environmental footprint
Use Better
Materials and Substances
Use Again
Repack and remanufacture
Documents
arrow2_down
Software and Firmware
arrow2_down
arrow2_down

Need more information? Check our technical FAQs!

Easily find answers to the most frequently asked questions.

  • Products Documentation
  • Software Downloads
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings