How can we help you today?
What is the cable pinout (RJ45 to RJ45) to connect a Compact 258/265/275/285 PLC to a 174CEV30010/20?
Issue
A serial communication cable is required between a Compact 258/265/275/285 and a CEV 300 10/20.
Product Line
- Compact 258/265/275/285
- CEV 300 10/20
Resolution
Wire the cable according to the following pinout:
| Compact 258/265/275/285 | Signal | Connection | CEV 300 10/20 | Signal |
|---|---|---|---|---|
| Pin 1 | +5 V | → | Pin 2 | DTR |
| Pin 2 | DSR | → | Pin 1 | NC |
| Pin 3 | TX | → | Pin 3 | RX |
| Pin 4 | RX | → | Pin 4 | TX |
| Pin 5 | GND | → | Pin 5 | GND |
| Pin 8 | Chassis GND | → | Pin 8 | NC |
In addition:
- On the Compact 258/265/275/285 side, bridge pin 6 (RTS) and pin 7 (CTS).
- On the CEV 300 10/20 side, bridge pin 6 (CTS) and pin 7 (RTS).
Released for: Schneider Electric Malaysia
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.