Issue:
ATS22 soft starter SLF fault
Product Line:
ATS22 series soft starters
Environment:
All models, All serial numbers.
Cause:
SLF is an indication of Serial Link Fault. The starter has lost communication with the Modbus network.
Resolution:
Ensure that the Modbus network is connected properly to the starter and the network is passing traffic and has not faulted. Ensure that the modbus address on the starter is set correctly.
If no modbus network is being used with this starter, check parameter CtrL under the COP menu. For Local control via the terminals, this parameter should be set to LCL (factory default). For Modbus control it should be set to DBS. Note that you will not have access to the COP menu unless parameter LAC under the CONF menu is set to ON.
ATS22 soft starter SLF fault
Product Line:
ATS22 series soft starters
Environment:
All models, All serial numbers.
Cause:
SLF is an indication of Serial Link Fault. The starter has lost communication with the Modbus network.
Resolution:
Ensure that the Modbus network is connected properly to the starter and the network is passing traffic and has not faulted. Ensure that the modbus address on the starter is set correctly.
If no modbus network is being used with this starter, check parameter CtrL under the COP menu. For Local control via the terminals, this parameter should be set to LCL (factory default). For Modbus control it should be set to DBS. Note that you will not have access to the COP menu unless parameter LAC under the CONF menu is set to ON.
Released for: Schneider Electric Malaysia




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.