Issue:
Magelis boots up slow due to some datalogging files (Dxxxxxx_OLD.dat)
Product Line:
XBTGC/GK/GT, HMIGTO/GTU/STO/STU, iPC
Resolution:
The data logging system has a mechanism to check the integrity of the data logging files. In the event it detects:
1) Corrupt data
2) Incompatible log formats (ie from an older version)
3) Data that was logged with a date or time in the future (ie, the clock was accidentally moved forward and then backwards)
the file will be renamed DXXXXXX_OLD.dat
The datalogging system will check these 3 conditions each time. Of course on an empty CF/SD card or USB flash drive, these conditions don't exist, so the boot up time is fast. However, if there is lots of data on the card, it will take a long time.
We recommend retrieving the data on the flash drive and format the drive.
Magelis boots up slow due to some datalogging files (Dxxxxxx_OLD.dat)
Product Line:
XBTGC/GK/GT, HMIGTO/GTU/STO/STU, iPC
Resolution:
The data logging system has a mechanism to check the integrity of the data logging files. In the event it detects:
1) Corrupt data
2) Incompatible log formats (ie from an older version)
3) Data that was logged with a date or time in the future (ie, the clock was accidentally moved forward and then backwards)
the file will be renamed DXXXXXX_OLD.dat
The datalogging system will check these 3 conditions each time. Of course on an empty CF/SD card or USB flash drive, these conditions don't exist, so the boot up time is fast. However, if there is lots of data on the card, it will take a long time.
We recommend retrieving the data on the flash drive and format the drive.
Released for: Schneider Electric Malaysia










Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.