Issue:
When running, the output Hz is displayed, but there is a flashing L before it.
Product Line:
Altivar 212 ATV212 S-Flex
Environment:
All models
Cause:
N/A
Resolution:
The flashing L is an alarm indicating that the motor overload timer has reached or exceeded 50% of it's detected fault level. Typically this is a pre-alarm that will eventually trip OL2, motor overload. Parameter tHr is the overload amp threshold and should typically be set to motor FLA. Monitor the motor amps in Monitoring Mode, Cxxx (xxx is amp numerical value). If a parameter correction is made, the L may continue to flash until the thermal memory clears the overload conditions.
When running, the output Hz is displayed, but there is a flashing L before it.
Product Line:
Altivar 212 ATV212 S-Flex
Environment:
All models
Cause:
N/A
Resolution:
The flashing L is an alarm indicating that the motor overload timer has reached or exceeded 50% of it's detected fault level. Typically this is a pre-alarm that will eventually trip OL2, motor overload. Parameter tHr is the overload amp threshold and should typically be set to motor FLA. Monitor the motor amps in Monitoring Mode, Cxxx (xxx is amp numerical value). If a parameter correction is made, the L may continue to flash until the thermal memory clears the overload conditions.
Released for: Schneider Electric Malaysia


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.