Issue:
ATV320 Unable to change the logic inputs in the I/O menu.
Product Line:
ATV320
Environment:
All
Cause:
Programming logic inputs
Resolution:
You can not assign a function to the logic inputs in I/O menu.
Those are read only parameters.
You must assign a logic input to the function you need.
Example, If you want to assign freewheel stop to LI2, you would need to go to CONF / FULL / FUN / STT, then go to NST and assign LI2 to NST.
ATV320 Unable to change the logic inputs in the I/O menu.
Product Line:
ATV320
Environment:
All
Cause:
Programming logic inputs
Resolution:
You can not assign a function to the logic inputs in I/O menu.
Those are read only parameters.
You must assign a logic input to the function you need.
Example, If you want to assign freewheel stop to LI2, you would need to go to CONF / FULL / FUN / STT, then go to NST and assign LI2 to NST.
Released for: Schneider Electric Malaysia




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.