Issue:
Disable Loc/ Rem buttons used with the integral and remote HMI (VW3A1101) on an ATV212 Drive
Product Line:
ATV212
Environment:
All serial numbers
Cause:
Unwanted function
Resolution:
The ATV212 integral keypad has a LOC/REM button.
The VW3A1101 Loc/Rem button is the F4 key. Note that just above F4, in the LCD display, the function is indicated as Loc/Rem. Pressing the F4 will toggle between Local and Remote modes. The current mode is shown above the F1 key. The F4 key mimics the integral keypad LOC/REM button.
Use parameter F732 to enable or disable both the F4 and LOC/REM keys.
F732 = 0 is [Permitted memo]: still retained with the power off. The current mode is maintained through a power cycle.
F732 = 1 is [Prohibited]: The F4 and Loc/Rem keys are disabled and the VFD is in Remote mode.
F732 = 2 is [Permitted no memo]: cancelled with the power off. The VFD will always power up in Remote mode.
Note that if the LOC/REM key is disabled, switching between local and remote mode can be achieved with parameters [Frequency mode sel] (FMOd) and [Command mode sel] (CMOd).
Disable Loc/ Rem buttons used with the integral and remote HMI (VW3A1101) on an ATV212 Drive
Product Line:
ATV212
Environment:
All serial numbers
Cause:
Unwanted function
Resolution:
The ATV212 integral keypad has a LOC/REM button.
The VW3A1101 Loc/Rem button is the F4 key. Note that just above F4, in the LCD display, the function is indicated as Loc/Rem. Pressing the F4 will toggle between Local and Remote modes. The current mode is shown above the F1 key. The F4 key mimics the integral keypad LOC/REM button.
Use parameter F732 to enable or disable both the F4 and LOC/REM keys.
F732 = 0 is [Permitted memo]: still retained with the power off. The current mode is maintained through a power cycle.
F732 = 1 is [Prohibited]: The F4 and Loc/Rem keys are disabled and the VFD is in Remote mode.
F732 = 2 is [Permitted no memo]: cancelled with the power off. The VFD will always power up in Remote mode.
Note that if the LOC/REM key is disabled, switching between local and remote mode can be achieved with parameters [Frequency mode sel] (FMOd) and [Command mode sel] (CMOd).
Released for: Schneider Electric Malaysia




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.