Issue:
Undercurrent fault setup on the Tesys T.
Product Line:
Tesys T
Environment:
North America
Cause:
Undercurrent fault
Resolution:
Under Parameter List, Current submenu, set undercurrent fault to enable (deactivate is default).
Undercurrent fault threshold min 30% of FLC (Full load current) to 100% FLC. Default is 50%.
Undercurrent fault timeout has a range of 1 to 200s with default timeout period of 10s.
Undercurrent warning activate allows undercurrent warning threshold to be programmed. 30 to 100%FLC as range and 50% FLC as default.
Undercurrent fault setup on the Tesys T.
Product Line:
Tesys T
Environment:
North America
Cause:
Undercurrent fault
Resolution:
Under Parameter List, Current submenu, set undercurrent fault to enable (deactivate is default).
Undercurrent fault threshold min 30% of FLC (Full load current) to 100% FLC. Default is 50%.
Undercurrent fault timeout has a range of 1 to 200s with default timeout period of 10s.
Undercurrent warning activate allows undercurrent warning threshold to be programmed. 30 to 100%FLC as range and 50% FLC as default.
Released for:Schneider Electric Malaysia

