1. Issue
In Unity Pro or EcoStruxure Control Expert software, the following popup could be displayed on TSX CPP 110 screen validation after selecting a *.co file of the Sycon tool:
“Cannot load configuration from the database specified!
Error when reading configuration from DBM file. (…)”
2. Product Line
Unity Pro / EcoStruxure Control Expert, Sycon, TSX CPP 110 CANopen PCMCIA card
3. Resolution
The complete name (path + file name) of the *.co file selected in the TSX CPP 110 screen must be less than or equal to 126 characters.
The directory containing the CANopen file must also have read/write access.
Released for: Schneider Electric Malaysia


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.