Issue:
Would multiple load reactors, chokes or filters be required when connecting more than one motor to the output an Altivar AC Drive or Process Drive?
Product Line:
Altivar or Altivar Process Drive
Environment:
All
Cause:
Multi motor application using motor filters / chokes.
Resolution:
In general the choke must be connected closest to the drive to have the best efficiency (less leakage current, …)
Per Level 3 in France, it is always recommended, per below, to use only one reactor, filter or choke for all motors.
Example below from ATV71, applies the other Altivar and Altivar Process Product Lines as well.
As you can see multiple chokes or filters will decrease the Efficiency of each motor.
Released for: Schneider Electric Malaysia
Issue:
Would multiple load reactors, chokes or filters be required when connecting more than one motor to the output an Altivar AC Drive or Process Drive?
Product Line:
Altivar or Altivar Process Drive
Environment:
All
Cause:
Multi motor application using motor filters / chokes.
Resolution:
In general the choke must be connected closest to the drive to have the best efficiency (less leakage current, …)
Per Level 3 in France, it is always recommended, per below, to use only one reactor, filter or choke for all motors.
Example below from ATV71, applies the other Altivar and Altivar Process Product Lines as well.
As you can see multiple chokes or filters will decrease the Efficiency of each motor.
Released for: Schneider Electric Malaysia
Need help?
Start here!
Find answers now. Search for a solution on your own, or connect with one of our experts.
Contact Support
Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Search FAQs
Search topic-related frequently asked questions to find answers you need.
Contact Sales
Start your sales enquiry online and an expert will connect with you.