Can I use the Unity Loader utility to upgrade the firmware of the BMENUA0100 OPC UA module?

No, The Unity Loader cannot be used for upgrading the firmware of the OPC UA module. You must use the EcoStruxure Automation Device Maintenance utility. You can download the utility and firmware file from the Schneider Electric public site at EcoStruxure Automation Device Maintenance V3.4.120 :https://www.se.com/us/en/download/document/EADM/

BMENUA0100 OPC UA module firmware: https://www.se.com/us/en/download/document/BMENUA0100_FIRMW_SV_02_04_02/