Can we change the speed reference from Percentage to Hertz when in Local on ATV320?
Issue:
Change the speed reference units from percentage to hertz when drive is being controlled in LOCAL (using the embedded dial)

Product Line:
ATV320 drives

Environment:
Altivar Drives

Cause:
Drive shows Percentage when giving a speed reference while running in LOCAL mode.

Resolution:

When running in LOCAL (AIU1) using only the embedded dial on the ATV320 drive, the speed reference is set in 0-100% of the speed range programmed on the drive.

It is NOT possible to change this to show Hertz (0-60 Hz) instead of Percentage (0-100%).

It is important to confirm what Menu are we seeing on the drive.

The Home Screen (where we have the RDY Status) changes to the output frequency of the motor once we provide a run command. RDY> 0.0-60.0 Hz. This is a read only parameter.

If we hit Enter (push the dial) once we will see the Reference Menu (Ref) we push enter again and we will see the Speed Reference value displayed in 0-100% and this is a value that can be modified when in Local Mode via the dial.

If we press ESC twice we go back to the Home screen where we can see the Output frequency value in Hertz.


If the application requires to only have the speed reference in Hertz, an option can be using a Remote display.

Option 1
VW3A1101 Graphic Display Keypad
VW3A1102 Remote Mount Bezel, IP54 (or the VW3A1105 if not being mounted)
VW3A1103 Optional Cover/Door for Bezel (increases rating to IP65)

Option 2
VW3A1111 Graphic Display Keypad
VW3A1112 Remote Mount Kit IP65
Both the ATV320 VFD and the VW3A1111 keypad firmware have been upgraded to support compatibility. (6-2019)
Firmware versions required:
ATV320-  V2.9IE37
VW3A1111-  V2.0IE51
Earlier versions are not compatible.

Then choose one cable to connect the remote keypad to the VFD:
VW3A1104R10 1meter
VW3A1104R30 3meter
VW3A1104R50 5meter
VW3A1104R100 10meter

Schneider Electric Malaysia

Can we change the speed reference from Percentage to Hertz when in Local on ATV320?
Issue:   
Change the speed reference units from percentage to hertz when drive is being controlled in LOCAL (using the embedded dial)

Product Line: 
ATV320 drives

Environment: 
Altivar Drives

Cause:  
Drive shows Percentage when giving a speed reference while running in LOCAL mode.

Resolution:

When running in LOCAL (AIU1) using only the embedded dial on the ATV320 drive, the speed reference is set in 0-100% of the speed range programmed on the drive. 

It is NOT possible to change this to show Hertz (0-60 Hz) instead of Percentage (0-100%).

It is important to confirm what Menu are we seeing on the drive. 

The Home Screen (where we have the RDY Status) changes to the output frequency of the motor once we provide a run command. RDY> 0.0-60.0 Hz. This is a read only parameter. 

If we hit Enter (push the dial) once we will see the Reference Menu (Ref) we push enter again and we will see the Speed Reference value displayed in 0-100% and this is a value that can be modified when in Local Mode via the dial. 

If we press ESC twice we go back to the Home screen where we can see the Output frequency value in Hertz. 


If the application requires to only have the speed reference in Hertz, an option can be using a Remote display.

Option 1
VW3A1101 Graphic Display Keypad 
VW3A1102 Remote Mount Bezel, IP54 (or the VW3A1105 if not being mounted)
VW3A1103 Optional Cover/Door for Bezel (increases rating to IP65)

Option 2
VW3A1111 Graphic Display Keypad
VW3A1112 Remote Mount Kit IP65
Both the ATV320 VFD and the VW3A1111 keypad firmware have been upgraded to support compatibility. (6-2019)
Firmware versions required:
ATV320-  V2.9IE37
VW3A1111-  V2.0IE51
Earlier versions are not compatible.

Then choose one cable to connect the remote keypad to the VFD:
VW3A1104R10 1meter
VW3A1104R30 3meter
VW3A1104R50 5meter
VW3A1104R100 10meter

Schneider Electric Malaysia

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:

Need help?

  • Start here!

    Find answers now. Search for a solution on your own, or connect with one of our experts.

  • Contact Support

    Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Search FAQs

    Search topic-related frequently asked questions to find answers you need.

  • Contact Sales

    Start your sales enquiry online and an expert will connect with you.

I'd like to receive news and commercial info from Schneider Electric and its affiliates via electronic communication means such as email, and I agree to the collection of information on the opening and clicks on these emails (using invisible pixels in the images), to measure performance of Schneider Electric's communications and to improve them. For more details, please read our Privacy Policy.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.