No. The “Transfer Test” feature of the ATS is designed to simulate loss of preferred power and initiate load transfer to the alternate power. Hence the term “Transfer” Test.

Released for: Schneider Electric Malaysia










Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.