The Network Variables List (NVL) communication works on the:
• Ethernet 1 port.
• Ethernet 2 port:
- if the Ethernet 1 port has a valid IP address and is connected to a device,
- or if the define ETH2_NVL_Communication has been entered in the Build tab of the Application Properties window.
NOTE: For more information about Compiler defines, refer to the EcoStruxure Machine Expert Programming Guide.
The define ETH2_NVL_Communication is only supported from Machine Expert V2.1.
About the TM241 connected to a TM4ES4:
The TM241 connected to a TM4ES4 has two different Ethernet networks. Each one gets its own and unique IP and MAC address.
The two Ethernet networks are called Ethernet 1 and Ethernet 2:
• Ethernet 1 is a single Ethernet port dedicated to communication between machines or with the control network.
• Ethernet 2 is a separate Ethernet port dedicated to device network connections.
For example, you can:
• Connect your PC to the Ethernet 1.
• Use a Modbus TCP I/O scanner with the Ethernet 2.
The Network Variables List (NVL) communication works on the:
• Ethernet 1 port.
• Ethernet 2 port:
- if the Ethernet 1 port has a valid IP address and is connected to a device,
- or if the define ETH2_NVL_Communication has been entered in the Build tab of the Application Properties window.
NOTE: For more information about Compiler defines, refer to the EcoStruxure Machine Expert Programming Guide.
The define ETH2_NVL_Communication is only supported from Machine Expert V2.1.
Released for: Schneider Electric Malaysia




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.