Problem
ViewX client fails to communicate with the server and the following error appears “ClearSCADA.Client.SecureSessionRequiredException”.

Solution
One of the common causes of ViewX client not able to connect to the server with error “ClearSCADA.Client.SecureSessionRequiredException” Is that the secure connection is set to false.
A workaround is to edit SYSTEMS.XML manually and change the secure field to "true". The folder can be located by default as follows C:\ProgramData\Schneider Electric\ClearSCADA. Please make sure to close ViewX client and shut down the server before editing the SYSTEMS.XML file.

Change SecureConnection= “false” to “true” as indicated below.

Once the editing is completed, save the changes and restart the ViewX client.
ViewX client fails to communicate with the server and the following error appears “ClearSCADA.Client.SecureSessionRequiredException”.
Solution
One of the common causes of ViewX client not able to connect to the server with error “ClearSCADA.Client.SecureSessionRequiredException” Is that the secure connection is set to false.
A workaround is to edit SYSTEMS.XML manually and change the secure field to "true". The folder can be located by default as follows C:\ProgramData\Schneider Electric\ClearSCADA. Please make sure to close ViewX client and shut down the server before editing the SYSTEMS.XML file.
Change SecureConnection= “false” to “true” as indicated below.
Once the editing is completed, save the changes and restart the ViewX client.
Released for: Schneider Electric Malaysia
Problem
ViewX client fails to communicate with the server and the following error appears “ClearSCADA.Client.SecureSessionRequiredException”.

Solution
One of the common causes of ViewX client not able to connect to the server with error “ClearSCADA.Client.SecureSessionRequiredException” Is that the secure connection is set to false.
A workaround is to edit SYSTEMS.XML manually and change the secure field to "true". The folder can be located by default as follows C:\ProgramData\Schneider Electric\ClearSCADA. Please make sure to close ViewX client and shut down the server before editing the SYSTEMS.XML file.

Change SecureConnection= “false” to “true” as indicated below.

Once the editing is completed, save the changes and restart the ViewX client.
ViewX client fails to communicate with the server and the following error appears “ClearSCADA.Client.SecureSessionRequiredException”.
Solution
One of the common causes of ViewX client not able to connect to the server with error “ClearSCADA.Client.SecureSessionRequiredException” Is that the secure connection is set to false.
A workaround is to edit SYSTEMS.XML manually and change the secure field to "true". The folder can be located by default as follows C:\ProgramData\Schneider Electric\ClearSCADA. Please make sure to close ViewX client and shut down the server before editing the SYSTEMS.XML file.
Change SecureConnection= “false” to “true” as indicated below.
Once the editing is completed, save the changes and restart the ViewX client.
Released for: Schneider Electric Malaysia




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.