In certain contexts, using the M580 PLC in control Expert version 15.1 to 15.3, it happens that the PLC does not restart in RUN even though the "Autorun" option is validated.

Illustration example, "autorun" option for BMEP582020
This problem only occurs when a configuration modification (addition/deletion of a module, a rack, etc.) is made and followed by an online build.
The only solution in this case is to do a "rebuild all" and transfer the application to the PLC.
This operating issue is corrected in version 16 of Control Expert.
Illustration example, "autorun" option for BMEP582020
This problem only occurs when a configuration modification (addition/deletion of a module, a rack, etc.) is made and followed by an online build.
The only solution in this case is to do a "rebuild all" and transfer the application to the PLC.
This operating issue is corrected in version 16 of Control Expert.
Released for: Schneider Electric Malaysia


Need help?
Start here!
Find answers now. Search for a solution on your own, or connect with one of our experts.
Contact Support
Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Search FAQs
Search topic-related frequently asked questions to find answers you need.
Contact Sales
Start your sales enquiry online and an expert will connect with you.