!!!Confidential Content
Issue
The following error is shown when an ION meter is opened in ION Setup using single device mode:
"Potential Security Risk. Certificate Error Summary. Detected an invalid security certificate in use. Certificate has expired. The certificate is not trusted because it is self-signed. Error code: RemoteCertificateNameMismatch, RemoteCertificateChainErrors. The security certificate is not trusted by your computer's operating system. This may be caused by a misconfiguration or an attacker intercepting your connection. Only press Proceed if you are sure the connection is secure."
Product Line
ION Meters
Environment
ION Setup
Cause
This message is caused when a meter is configured to use Secure ION, or ION over TLS. By default, devices that support Secure ION include a self-signed SSL certificate. If using ION Setup single device mode, you must accept the certificate every time you connect to the device using ION Setup.
Resolution
To increase security and prevent this message from re-appearing in single device mode, use a Certificate Authority (CA). This can be provided by IT.
For more information on secure ION, see the PM8000 online guide https://product-help.schneider-electric.com/PowerLogic-PM8000/en-us/content/03-communications/secure-ion.htm?tocpath=Communications|ION|Secure ION|_____0
Released for: Schneider Electric Malaysia
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.
50多年来,施耐德电气一直引领配电创新。我们不断重新定义配电,以帮助您充分利用全新的分散化、低碳化和数字化能源模式。
EcoStruxure配电是我们的最新发展- 数字化、开放式架构,使我们的合作伙伴和客户能够轻松利用配电领域的最新突破技术,将可靠性、安全性、效率、可持续性和互联互通性提升至新高度。
借助施耐德电气EcoStruxure配电,您可以在一个架构与平台上获得数字化、互联互通的产品、应用、分析与服务等解决方案。