How to read timestamped input of a BMXERT1604 module ?
Issue:
How to retrieve the timestamp of an input located in a BMXERT1604T module
Product Line:
BMXERT1604, M580 CPU
Environment:
EcoStruxure Control Expert V16.2, Windows 10
Resolution:
The GET_TS_EVT_M function block gets the time stamped data in:
-
BMX ERT 1604T when located in Modicon M340 local drop
-
BMX ERT 1604T when located in Modicon M580 local and remote drops
-
BME P58 Modicon M580 controller
-
BMX CRA 312 10 of a Modicon M580
-
BME CRA 312 10 of a Modicon M580
This function allows reading the event buffer to make it available for the controller application:
To launch the communication function only once, the ENABLE signal needs to be reset to 0 after the ACTIVE parameter is set to 0. If the ENABLE parameter is maintained to 1 after the ACTIVE parameter is set to 0, the communication function is launched again and the ACTIVE parameter is set to 1 on the next cycle.
If the ENABLE bit is reset to 0 before completion, the function block is stopped (active bit to 0). To have a complete block execution, the value of 1 must be applied on the ENABLE bit until the operation has finished or until an error has occurred.
- The ADR pin must be connected to an ADDMX or ADDM function.
- The BUFFER array will contain the event timestamp entries, retrieved from the BMXERT1604 module.
Attached a description of the GET_TS_EVT_M function
To configure the BMXERT1604 on an M580, please follow this video : Video: How to configure a BMXERT1604 Timestamp module in an M580 application | Schneider Electric Belgium
Released for: Schneider Electric Malaysia
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.