RemoteConnect Logic Status Code: -8463 (16#DEF1) Character String Transfer Alert.
What is a Character String Transfer Alert?
A Character String Transfer Alert occurs when a string operation attempts to:
- Transfer more characters than the destination string can hold.
- Copy data into a string that exceeds the maximum configured length.
- Concatenate multiple strings and exceed the destination string capacity.
- Receive malformed string data from an external device
How to diagnose in Logic Editor (Control Expert).
- Go to Mode menu and then connect to the device.
- Go to Tools menu and select Diagnostic Viewer
Examine the Diagnostic Viewer window and it will provide the location of the error in the program.
In this example program, the variable "Result_String" was set to default 16 characters limit which was causing the issue.
Assigned Variables:
Program:
To correct the issue, increase the variable "Result_String" to have a 32 character limit by changing the Type to String[32]
Summary
The RemoteConnect String Overflow Error corresponds to Control Expert's Character String Transfer Alert (-8463 / 16#DEF1). The alert occurs when a string operation attempts to move, copy, or build a string larger than the available destination size. To diagnose the issue, monitor %S15, inspect string handling logic, review communication data received from RemoteConnect, and verify that all PLC string variables are sized appropriately.
Released for: Schneider Electric Malaysia
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.