Is it ok to use an ATS48 with a Corner Grounded Delta, Ungrounded Delta, or Open Delta system?

Article available in these languages: Spanish

Issue:
Will an ATS48 run with a Corner Grounded Delta, Ungrounded Delta, or Open Delta system

Product Line:
 ATS48

Environment:
 Corner Grounded, Ungrounded Delta, Open Delta system

Cause:
 n/a

Resolution:
It is ok to use Corner Grounded Delta with an ATS48 as long as the voltage is balanced phase to phase.
However, some problems may occur on Ungrounded systems. One or more phases may have a high voltage with respect to ground and may cause measurement irregularities that can affect the operation of the soft starter.
The Open Delta may be a problem because the voltage may not be balanced when loaded. This may cause phase fault problems.




CTA-ID : 2023862

Schneider Electric Nigeria

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.